General specifications | |
|---|---|
| Rated operating distance | 50 mm |
| Installation | non-flush |
| Output polarity | AC |
| Assured operating distance | 0 ... 40.5 mm |
| Reduction factor rAl | 0.4 |
| Reduction factor rCu | 0.3 |
| Reduction factor r304 | 0.85 |
| Output type | 2-wire |
Nominal ratings | |
| Operating voltage AC | 20 ... 253 V |
| Switching frequency | 0 ... 20 Hz |
| Hysteresis | 3 ... 15 % 5 % typical |
| Voltage drop | ? 5 V |
| Momentary current (20 ms, 0.1 Hz) | max. 4000 mA |
| Operating current | 5 ... 500 mA |
| Off-state current | 0.3 ... 1 mA typ. 0.7 mA |
| Time delay before availability | ? 100 ms |
| Operating voltage indicator | LED, green |
| Switching state indicator | LED, yellow |
Compliance with standards and directives | |
| Standard conformity | |
Approvals and certificates | |
| CCC approval | Certified by China Compulsory Certification (CCC) |
Ambient conditions | |
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
Mechanical specifications | |
| Connection type | 1/2"-20 UN , 3-pin |
| Housing material | PBT/base of metal |
| Sensing face | PBT |
| Housing base | metal |
| Degree of protection | IP68 |
| Note | 1) In the temperature range below 0 °C, permissible operating voltage Ub 80...253 V Safety fuse ? 2A (quick-blow) according to IEC60127-2 Sheet1 Recommendation: after a short circuit, check that the device is functioning correctly. |
8 (029) 555-8-000 | |
8 (044) 555-8-000 | |
8 (017) 255-8-000 |