Technical data | EP6228-3132 |
---|
Data transfer rates | 4.8 kbaud, 38.4 kbaud and 230.4 kbaud |
Connection method | M12, screw type |
Specification version | IO-Link V1.1, 4 x Class A, 4 x Class B |
IO-Link interfaces | 8 |
Nominal voltage | 24 V DC (-15 %/+20 %) |
Distributed clocks | – |
Cable length | max. 20 m |
IO-Link sensor supply L+ | 24 V DC, 1.4 A per port, ∑ 11.2 A |
IO-Link sensor supply 2L+ | 24 V DC, max. 4.0 A per port, ∑ 4.0 A for 2 ports each for Class B |
Current consumption from US | typ. 130 mA + load |
Power supply connection | feed: 1 x 7/8" plug, 5-pin; downstream connection: 1 x 7/8" socket, 5-pin |
Electrical isolation | 500 V |
Special features | Class A ports: 1, 2, 5, 6; Class B ports: 3, 4, 7, 8 |
Weight | approx. 250 g |
Operating/storage temperature | -25…+60 °C/-40…+85 °C |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. class/installation pos. | IP 65/66/67 (conforms to EN 60529)/variable |
Approvals/markings | CE, UL in preparation |